Heat Tracing Cable
Thermon
VSX - 15, 32, 48 and 64w/m
ATEX & IECEx Certified for Zone 1 & Zone 2 Hazardous Areas
Suitable for Process Temperature Maintenance
Thermon VSX heat tracing cables are self-regulating and capable of maintaining process temperatures up to 150ºC. It can also be used in areas which are subject to steam purging due it's high maximum exposure temperature of 250ºC.
VSX heat tracing cable is available in 4 variations providing power outputs from 15w/m up to 64w/m (at 10ºC) enabling it to be used for applications from frost protection to process temperature maintenance and will never overheat or waste energy due to it's self-regulating technology. This also means that the cable can be overlapped onto itself if required without risk.
The heat tracing cable is part of the Thermon Industrial heating range and is ideal for manufacturing factories, plant rooms, distilleries, pharmaceutical laboratories and many more and is ATEX and IECEx certified for use within potentially explosive atmospheres and hazardous areas.
Part Number 230V AC Nominal |
Power Output at 10ºC |
---|---|
VSX 5-2 | 15 watts per metre |
VSX 10-2 | 32 watts per metre |
VSX 15-2 | 48 watts per metre |
VSX 20-2 | 64 watts per metre |
Pictured: Thermon VSX Heat Tracing Cable Power Output Chart
Available Watt Densities | 15, 32, 48, 64 watts per metre at 10ºC |
---|---|
Nominal Supply Voltage |
230VAC Option - 110VAC - Contact T&D for further information |
Maximum Maintenance Temperature | 150ºC |
Maximum Continuous Exposure Temperature |
Intermittent Power On - 232ºC Intermittent Power Off - 250ºC Continuous Power Off - 204ºC |
Minimum Installation Temperature | -60ºC |
Minimum Bend Radius |
At -15ºC - 10mm At -60ºC - 32mm |
Construction |
Nickel-Plated Copper Bus Wires (2.1mm²) Semiconductive Heating Matric and Fluouropolymer Dielectric Insulation Nickel-Plated Copper Braid Fluoropolymer Overjacket provides additional protection to cable and braid where exposure to chemicals or corrosives is expected. |
T-Rating |
15, 32, 48 and 64 watts per metre - T3 200ºC Based on stabilised design - T4 to T6 |
Certification |
ATEX & IECEx II 2 G/D Ex e II T3 |