The Thermon Terminator ZT is a hazardous area thermostat designed to provide adjustable control for frost protection and temperature maintenance trace heating applications which require pipewall or tankwall temperature sensing.
The Terminator ZT is available with 4 different temperature control and bulb exposure temperature ranges and also has two variations.
The ZT-WP is designed to be wall mounted as standard, or pipe-mounted using a XP-1 stainless steel mounting bracket and has a PVC coated galvanised steel flexible capillary armouring complete with capillary gland and insulation entry device.
The ZT-XP includes an expeditor to allow for the thermostat to be installed directly onto the pipe and allows for two heating cables to enter and be connected within the enclosure.
Terminator ZT thermostats are suitable for either safe or ATEX Zone 1 and Zone 2 hazardous applications and have an IP rating of IP66.
Construction |
Junction Box - Glass reinforced polymer with DIN rail mounted terminal blocks Pipe-Mount Expediter - Glass reinforced polymer Capillary Temperature Sensor |
---|---|
Enclosure Rating | IP66 |
Maximum Pipe Exposure Temperature | 250ºC |
Minimum Installation Temperature | -60ºC |
Operating Ambient Temperature |
-60ºC ≤ Ta ≤ +55ºC - 16 Amps Max, T6 85ºC -60ºC ≤ Ta ≤ +50ºC - 25 Amps Max, T5 100ºC |
Maximum Voltage Rating | 250 VAC nominal up to 253 Vac |
Switch Rating | 25A (Ohmic, NC contact) |
Switch Type | Controller |
Electrical Connection | Terminal Block |
Adjustable Control Range |
ZT-C-100: 0ºC to 100ºC ZT-C-200: 0ºC to 200ºC ZT-C-300: 0ºC to 300ºC ZT-C-500: 20ºC to 500ºC |
Maximum Control Differential / Accuracy |
ZT-C-100: 7% / -1K to +7K ZT-C-500: 2.5% / -2K to +28K |
Maximum Bulb Exposure Temperature |
ZT-C-100: 230ºC ZT-C-500: 530ºC |
Bulb Dimensions |
ZT-C-100: 6mm x 76mm ZT-C-500: 6mm x 280mm |
Bulb Material | Stainless Steel |
Capillary Length | 1m |
Maximum Electrical Switching Frequency | 180 cycles / hour |
Electrical Durability Operating Cycles | Minimum 100,000 cycles |
Mechanical Durability Operating Cycles | Minimum 300,000 cycles |
Certification |
CENELEC - European Organisation for Electrotechnical Standardisation - Hazardous (Classified) Locations
Ex II 2 G Ex db eb IIC T5-T6 FM10ATEX0058X II 2 D Ex tb IIIC T100ºC-T85ºC |