Thermon TC2 & TC2/XP Plus - Pipewall Sensing Thermostat with Limiter

Thermon TC2 & TC2/XP Plus - Pipewall Sensing Thermostat with Limiter

Pipewall Sensing Trace Heating Thermostat for Non-Hazardous Area Applications

Thermon’s TC2 & TC2/XP Plus are pipewall sensing thermostats for frost protection and temperature maintenance trace heating systems where a high temperature limiter is also required.

The first thermostatic switch energises the heating cable below the controller setpoint, whilst the second switch de-energises if the temperature sensed exceeds the limiter setpoint.

The TC2 is designed to be wall mounted as standard but can be pipe mounted using an optional Thermon XP-1 stainless steel mounting bracket. The TC2 also comes with a PVC coated galvanised steel flexible capillary armouring complete with capillary gland and insulation entry device.

The TC2/XP Plus includes an expediter to allow for the thermostat to be installed directly onto the pipe and allows for one trace heating cable to enter and be connected within the enclosure.

On both the TC2 and TC2/XP Plus there are indication lamps for power-on and heater-on which are visible through a transparent cover. Both thermostats have non-metallic enclosures which are suitable for harsh industrial applications and are certified IP65 for protection against water and dust ingress.

Thermon TC2 & TC2/XP Plus - Pipewall Sensing Thermostat - Technical Specification
Voltage Rating 400 VAC
Switch Rating

230 VAC: 16A (Ohmic, NC contact)

400 VAC: 10A (Ohmic, NC contact)

Switch Type SPDT
Operating Ambient Temperature -30ºC to +55ºC
Electrical Connection Terminal Block
Bulb Material Stainless Steel
Capillary Length 1m
Weight Approx 1.5kg
Product Type

Controller

TC2-1-40/XXX

TC2-1-120/XXX

TC2-1-300/XXX

 

Limiter

TC2-1-XXX/120

TC2-1-XXX/300

Adjustable Range TC2-1-40/XXX: 0ºC to 40ºC
TC2-1-120/XXX: 20ºC to 120ºC
TC2-1-300/XXX: 50ºC to 300ºC

 

TC2-1-XXX/120: 20ºC to 120ºC
TC2-1-XXX/300: 50ºC to 300ºC

Max On/Off Differential

TC2-1-40/XXX: +/-4ºC
TC2-1-120/XXX: +/-4ºC
TC2-1-300/XXX: +/-10ºC

 

TC2-1-XXX/120: +/-4ºC
TC2-1-XXX/300: +/-10ºC

Max Bulb Temperature

TC2-1-40/XXX: 130ºC
TC2-1-120/XXX: 145ºC
TC2-1-300/XXX: 320ºC

 

TC2-1-XXX/120: 145ºC
TC2-1-XXX/300: 320ºC

Bulb Size

TC2-1-40/XXX: 6mm x 140mm
TC2-1-120/XXX: 6mm x 140mm
TC2-1-300/XXX: 4mm x 165mm

 

TC2-1-XXX/120: 6mm x 140mm
TC2-1-XXX/300: 4mm x 165mm

 