Solar Tempering Thermostatic Mixing Valves

Thermostatic Mixing Valves for Solar Hot Water Distribution Systems

Reliance Water Controls provide solar tempering thermostatic mixing valves designed to withstand the extreme thermal demands of solar heating applications.

Solar Tempering valves are available in two variations - Highflow and Universal, both are used to mix hot and cold water to deliver tempered water at a constant temperature throughout an entire house, building or system.

Solar Tempering Valves Thermostatic Mixing Valves

The Highflow Solar Tempering Valve is more suited to high flow, large capacity applications and for low pressure environments such as gravity fed and tank supplied solar water heater installations.

The Universal Solar Tempering Valve is ideal for domestic applications where there are fluctuations in supply conditions and in solar hot water installations where a booster pump is used.

Solar Tempering Thermostatic Mixing Valves Product Range
Part Ref Description

Dimensions

(mm unless otherwise stated)

A B C D E F G
Heat 115 090 Solar Highflow Tempering Valve - 22mm Compression 183 65 58 82 184 57 1" BSP
Heat 110 092 Solar Universal Tempering Valve - 15/22mm Compression 142 47 53 77 162 40 1" BSP

Solar Tempering Valves Thermostatic Mixing Valve - Dimensions Heat 110 092 Valve

Solar Tempering Valves Thermostatic Mixing Valve - Dimensions Heat 115 090

Solar Tempering Thermostatic Mixing Valves Technical Specification
Body Material Cast Gunmetal, nickel plated
Internal Components DZR Brass
Seals Nitrile Elastomer
Spring & Strainers Stainless Steel
Piston Polysulfone Polymer
Fittings DZR Brass
Temperature Setting Range 30-65ºC
Optimum Outlet Temperature Range

40-50ºC

Note: Must be commissioned on site to acheive desired outlet temperature

Hot Supply Temperature 60-99ºC
Cold Supply Temperature 5-30ºC
Minimum Temperature Differential 10ºC
Nominal Temperature Stability +/- 3%
Static Pressure 16 bar max
Operating Pressure 0.2 to 5.0 bar
Minimum Flow Rate 4L per minute
Maximum Pressure Loss Ratio

10:1 (Either Supply)

Note - Optimum performance achieved with equal pressure

Solar Tempering Valves Thermostatic Mixing Valve Performance Chart