Heatguard Planar Thermostatic Mixing Valves

WRAS Approved Group Thermostatic Mixing Valves

Reliance Water Control’s Heatguard Planar range is a group thermostatic mixing valve for high flow rate group mixing applications.

Heatguard Planar thermostatic mixing valves are ideal for multiple outlet shower or basin installations where stable outlet temperatures at varying flow rates are important.

Heatguard Planar Thermostatic Mixing Valve - WRAS Approved

The Heatguard Planar thermostatic mixing valve has two quick reaction wax thermostats to provide temperature control and has an optional user-adjustable or tamperproof function to provide the user with flexible control and is WRAS approved.

The Heatguard Planar mixing valve comes with 4-in-1 fittings comprising of a full flow, chrome-plated ball type isolating valve and high flow barrel type strainer which protects the check cartridge/non-return valve from system contamination. 

Additionally a ¼” BSP test point is included to allow for the monitoring of system conditions such as temperature, pressure and cross-flow.

Heatguard Planar Thermostatic Mixing Valve

For ease of installation the valve is supplied with compression connections on both the inlets and the outlet.

Heatguard Planar Thermostatic Mixing Valves Product Range
Part Ref Description

Dimensions

(mm unless otherwise stated)

A B C D E F G H
Heat 230 100 Heatguard Planar 230 15mm 4-in-1 100 85 185 250 25 70 125 ¾" BSP
Heat 330 100 Heatguard Planar 330 22mm 4-in-1 135 105 245 320 30 95 127 1" BSP
Heat 430 100 Heatguard Planar 430 28mm 4-in-1 170 125 275 355 40 105 127 1" BSP
Heat 530 100 Heatguard Planar 530 28mm 4-in-1 with 35mm outlet 180 125 275 355 40 105 127 1 ¼" BSP

Heatguard Planar Thermostatic Mixing Valve Dimensions

Heatguard Planar Thermostatic Mixing Valves Technical Specification
Factory Set Temperature 41ºC
Temperature Setting Range 38-46ºC
Hot Supply Temperature 52-85ºC
Cold Supply Temperature 5-20ºC
Nominal Temperature Stability +/- 3ºC
Static Pressure 16 bar max
Operating Pressure 0.2 to 3.5 bar
Pressure Variation +10% Max
Maximum Pressure Loss Ratio

2:1 (Either Supply)

Note - Optimum performance acheived with equal pressure

Heatguard Planar Thermostatic Mixing Valve Flow Characteristics