Heatguard LS2 Thermostatic Mixing Valves - TMV2

TMV2 and WRAS Approved Thermostatic Mixing Valves

Reliance Water Controls Heatguard LS2 is a thermostatic mixing valve which is ideal for retrofit applications due to the L shape of the valve.

This design means that the hot water port and mixed outlet ports are opposite from each other reducing the need for pipework modifications.

Heatguard LS2 Thermostatic Mixing Valve - TMV2 ApprovedHeatguard LS2 Thermostatic Mixing Valve - WRAS Approved

The compact shape of the Heatguard LS2 allows for the TMV to be hidden behind a pedestal basin.

The LS2 thermostatic mixing valve is TMV2 approved for use within domestic and commercial or general public applications and is also WRAS approved and complies with BS EN 1111 regulations.

The Heatguard LS2 TMV provides stable mixed water temperature control and has a rapid failsafe on either hot or cold water supply in the event of supply failure.

Heatguard LS2 Thermostatic Mixing Valve

Reliance Water Controls Heatguard LS2 TMV2 Thermostatic Mixing Valves Features

  • L pattern valve is simple to install and service
  • Tamperproof setting adjustment
  • Protection against dirty systems via integral strainers
  • Protection against cross flow via check valves
Heatguard LS2 Thermostatic Mixing Valves Product Range
Part Ref Description

Dimensions

(mm unless stated otherwise)

A B C D E F G H
Heat 260 500 15mm Heatguard LS2

144

73

145

60

45

¾" BSP 15 45

Heatguard LS2 Thermostatic Mixing Valve Dimensions

Heatguard LS2 Thermostatic Mixing Valves Technical Specification
Body Material Gunmetal
Seals Nitrile
Spring & Strainers Stainless Steel
Piston Polysulfone
Fittings DZR Brass
Factory Set Temperature 38ºC
Temperature Setting Range 38-48ºC
Hot Supply Temperature 52-90ºC
Cold Supply Temperature 5-20ºC
Minimum Temperature Differential 15ºC
Nominal Temperature Stability +/-2ºC
Static Pressure 16 bar max
Minimum Working Pressure 0.5 bar
Operating Pressure 1.0 to 5.0 bar
Minimum Flow Rate 4L per minute
Flow Rate at 1 Bar Pressure Loss 15L per minute
Maximum Pressure Loss Ratio

2:1 (Either Supply)

Note - Optimum performance achieved with equal pressure

Heatguard LS2 Thermostatic Mixing Valve Flowrate Graph