Thermon RSX 15-2 Heat Tracing Cable

Heat Tracing Cable

Thermon RSX 15-2

ATEX & IECEx Certified for Zone 1 & Zone 2 Hazardous Areas

ATEX & IECEX Heat Tracing Cables

Thermon RSX 15-2 heat tracing cable is well suited to frost protection applications where high heat losses are encountered and it is vital to prevent freezing from occurring or to rapidly thaw ice. In particular RSX 15-2 cable is DNV (Det Norske Veritas) approved for anti-icing and de-icing on ships and offshore platforms.

 

Thermon RSX 15-2 Heat Tracing Cable

The heat tracing cable provides a heat output of 48w/m at 10ºC and can be installed in environments such ship hand rails and deck surfaces in temperatures as low as -60ºC. RSX heat tracing cable can maintain temperatures up to 65ºC and has a maximum exposure temperature of 85ºC. This means that the cable cannot be subject to steam purging, however the construction of the cable provides protection against aqueous inorganic chemicals, organic chemicals and corrosives. 

As the cable is self-regulating it can be overlapped onto itself without risk of overheating or wasting energy and has a maximum circuit length of 112m. 

RSX 15-2 heat tracing cable is part of the Thermon Industrial heating range and can also be for manufacturing factories, plant rooms, distilleries, pharmaceutical laboratories and many more and is ATEX and IECEx certified for use within Zone 1 & Zone 2 hazardous areas.

Thermon RSX 15-2 Heat Tracing Cable - Technical Specification
Cable Watt Density 48w/m 10ºC
Nominal Supply Voltage

230VAC

Option - 110VAC - Contact T&D for further information

Maximum Maintenance Temperature 65ºC
Maximum Continuous Exposure Temperature Power Off - 85ºC
Minimum Installation Temperature

RSX with OJ  -50ºC

RSX with FOJ Option -60ºC

Minimum Bend Radius

At -15ºC - 10mm

At -50ºC for OJ and at -60ºC for FOJ - 32mm

Construction

Nickel-Plated Copper Bus Wires (2.1mm²)

Radiation Cross-Linked Semiconductive Heating Matrix

Radiation Cross-Linked Dielectric Insulation

Tinned Copper Braid

Polyolefin overjacket provides additional protection where exposure to aqueous inorganic chemicals is expected

Optional FOJ Fluoropolymer overjacket provides additional protection where exposure to organic chemicals or corrosives is expected

T-Rating

RSX with OJ, based on stabilised design - T4 to T5

RSX with FOJ option - T5

Certification

ATEX & IECEx Certified II 2 G T4 to T5

Pictured: Thermon RSX 15-2 Heat Tracing Cable Power Output Chart