Nelson MI Heat Tracing Cable

Heat Tracing Cable

Nelson MI - Up to 88w/ft

ATEX & IECEX Heat Tracing CableNelson MI heat tracing cables are custom made and mineral insulated and are especially suited to high temperature process maintenance applications and can be exposed to temperatures up to 1100ºF / 593ºC.

Pictured: Nelson MI Heat Tracing Cables - Suitable for Hazardous Area Process Temperature Maintenance

Nelson MI Heat Tracing Cable

MI heat tracing cables are manufactured with an Alloy 825 outer sheath and can be used for hazardous area applications with power outputs up to a maximum of 88 watts per ft and supply voltages up to 600VAC.

Nelson MI Mineral Heat Tracing Cable - Technical Specification
Cable Type K1 K2 B2
Sheath Material Alloy 825
Cable Diameter

0.1875"

(4.76mm)

0.3125"

(7.94mm)

Number of Conductors 1 2
Maximum Voltage 600VAC 300VAC 600VAC
Maximum Exposure Temperature 1100ºF / 593ºC
Maximum Power Output 62 w/ft (204 w/m) 88 w/ft (289 w/m)
Weight

0.07lbs/ft

(0.0104 kg/m)

0.22 lbs/ft

(0.327 kg/m)

Standard Cold Lead 7ft / 2.1m

Pictured: Nelson MI Heat Tracing Cable Resistance vs Temperature Multiplier Graph

Nelson MI Heat Tracing Cable Resistance vs Temperature Multiplier Graph

Pictured: Nelson MI Heat Tracing Cable Maximum Wattage Under Insulation Graph

Nelson MI Heat Tracing Cable Maximum Wattage Under Insulation Graph

Pictured: Nelson MI Heat Tracing Cable Maximum Wattage Outside Insulation Graph

Nelson MI Heat Tracing Cable Maximum Wattage Outside Insulation Graph