Nelson LT Heat Tracing Cable

Heat Tracing Cable

Nelson LT - 3, 5 8 & 10w/ft

Nelson LT heat tracing cable which is designed to provide a method of frost protection to metallic and plastic pipes within Zone 1 & Zone 2 hazardous area applications.

ATEX & IECEX Heat Tracing CableThe heat tracing cable can maintain temperatures up to 65ºC and can be exposed to temperatures up to 85ºC with a maximum circuit length of 650ft.

Pictured: Nelson LT Heat Tracing Cable - Suitable for Hazardous Area Frost Protection

Nelson LT Heat Tracing Cable

LT heat tracing cables are self regulating which ensures that the cable never overheats or wastes energy and can even be overlapped if necessary.

The heat tracing cable is available in 8 variations providing power outputs of 3, 5, 8 and 10 watts per ft at 10ºC using either a 120VAC or 240VAC supply voltage.

Nelson LT Heat Tracing Cable - Product Range
Part Ref

Supply

Voltage

Watts

per Foot

T

Rating

LT3 120VAC 3 watts per ft T6
LT23 240VAC 3 watts per ft T6
LT5 120VAC 5 watts per ft T6
LT25 240VAC 5 watts per ft T6
LT8 120VAC 8 watts per ft T5
LT28 240VAC 8 watts per ft T5
LT10 120VAC 10 watts per ft T5
LT210 240VAC 10 watts per ft T5

Pictured: Nelson LT Heat Tracing Cable Power Output Chart

Nelson LT Heat Tracing Cables Power Output Chart

Nelson LT Heat Tracing Cable - Circuit Breaker Selection

Supply 

Voltage

Part Ref

Start Up Temp

Max Total Length 

vs Circuit Breaker Size

15A 20A 30A 40A
120VAC LT3 50ºF / 10ºC 325ft N/A N/A N/A
0ºF / -18ºC 230ft 305ft 325ft N/A
-20ºF / -29ºC 205ft 275ft 325ft N/A
LT5 50ºF / 10ºC 225ft 270ft N/A N/A
0ºF / -18ºC 155ft 205ft 270ft N/A
-20ºF / -29ºC 135ft 180ft 270ft N/A
LT8 50ºF / 10ºC 145ft 195ft 210ft N/A
0ºF / -18ºC 100ft 130ft 195ft 210ft
-20ºF / -29ºC 90ft 115ft 175ft 210ft
LT10 50ºF / 10ºC 115ft 150ft 180ft N/A
0ºF / -18ºC 85ft 110ft 155ft 180ft
-20ºF / -29ºC 75ft 100ft 145ft 180ft
230VAC LT23 50ºF / 10ºC 650ft N/A N/A N/A
0ºF / -18ºC 460ft 620ft 650ft N/A
-20ºF / -29ºC 410ft 550ft 650ft N/A
LT25 50ºF / 10ºC 460ft 540ft N/A N/A
0ºF / -18ºC 310ft 415ft 540ft N/A
-20ºF / -29ºC 275ft 370ft 540ft N/A
LT28 50ºF / 10ºC 295ft 390ft 420ft N/A
0ºF / -18ºC 200ft 265ft 395ft 420ft
-20ºF / -29ºC 175ft 235ft 350ft 420ft
LT210 50ºF / 10ºC 230ft 305ft 360ft N/A
0ºF / -18ºC 165ft 220ft 325ft 360ft
-20ºF / -29ºC 150ft 195ft 290ft 360ft

UK Time - GMT:

LT Heat Tracing Cable
Nelson LT Heat Tracing Cable

Heat Tracing - Thorne & Derrick