Meynell 15/3 Thermostatic Mixing Valves
A ½" thermostatic mixing valve with integral check valves and strainers, suitable for under-basin installation and providing thermostatic shutdown in less than 2 seconds.
The unit also incorporates tamper proof temperature adjustment.
Operation:
- Designed to be installed into the supply pipework and must be used with a separate outlet flow control such as a tap.
Connections:
- Inlet and outlet: 15 mm compression fittings.
Pressure:
- Minimum operating pressure: 0.1 bar.
- Maximum static pressure: 10 bar.
- Maximum pressure loss ratio: 10:1 (in favour of either supply).
- Maximum hot water supply temperature: 85°C.
- Maximum cold water supply temperature: 25°C.
Note: Both hot and cold pressures should be nominally equal.
Temperature range:
- Factory pre-set maximum outlet temperature: 42°C.
- Minimum temperature differential between hot inlet and pre-set outlet temperature: 10°C.
- Optimum temperature control range: 35–45°C.
- Maximum hot water temperature: 85°C (for safety reasons it is recommended that the hot water storage temperature is maintained at between 60°C and 65°C in ablutionary applications).
Body Materials:
- DZR brass housed in white plastic casing.