Thermon KSX Heat Tracing Cable

Heat Tracing Cable

Thermon

KSX - 15, 31, 48 and 64w/m

ATEX & IECEx Certified for Zone 1 & Zone 2 Hazardous Areas

Suitable for Process Temperature Maintenance

ATEX & IECEX Heat Tracing Cable

 

 

Thermon KSX heat tracing cables are self-regulating and capable of being maintaining temperatures up to 121ºC and is ATEX and IECEx certified allowing it to be used within potentially explosive atmospheres.

Pictured: Thermon KSX Heat Tracing Cable - Suitable for Hazardous Area Process Temperature Maintenance up to 121ºC 

Thermon KSX Heat Tracing Cable

The KSX heat tracing cable comes in 4 variations providing power outputs from 15w/m up to 64w/m (at 10ºC) allowing it to be used in high temperature process maintenance applications but is not suitable for steam purging. The self-regulating aspect of the cable ensures that the cable will never overheat or waste energy and can even be overlapped onto itself.

The heat tracing cable is part of the Thermon Industrial heating range and is ideal for manufacturing factories, plant rooms, distilleries, pharmaceutical laboratories and many more and due to it's ATEX and IECEx certifications it can be used within Zone 1 & Zone 2 hazardous areas.

Typical KSX Heat Tracing Applications Include:

  • Process Temperature Maintenance
  • Pipe Frost Protection
  • Tank Heating
  • Hopper Heating
  • Vessel Heating
  • Long Line Trace Heating
Thermon KSX Heat Tracing Cable - Product Range
Part Number Power Output at 10ºC
KSX 5-2 15 watts per metre at 10ºC
KSX 10-2 31 watts per metre at 10ºC
KSX 15-2 48 watts per metre at 10ºC
KSX 20-2 64 watts per metre at 10ºC

Pictured: Thermon HSX Heat Tracing Cable Power Output Chart 

Thermon KSX Heat Tracing Cable Power Output Chart

Thermon KSX Heat Tracing Cable - Technical Specification
Available Watt Densities 15, 31, 48 and 64 watts per metre at 10ºC
Nominal Supply Voltage

230V AC

Option - 110VAC - Contact T&D for further information

Maximum Maintenance or Exposure Temperature Continuous Power On - 121ºC
Minimum Installation Temperature -60ºC
Minimum Bend Radius

At -15ºC - 10mm

 

At -60ºC - 32mm

Construction

Nickel-Plated Copper Bus Wires (1.3mm²)

 

Semiconductive Heating Matrix and Fluoropolymer Dielectric Insulation

Tinned Copper Braid

Fluoropolymer overjacket provides additional protection to cable and braid where exposure to chemicals or corrosives is expected

T-Rating Based on stabilised design - T3 to T6
Certification

ATEX & IECEx II 2 G

Ex e II T3 to T6

II 2 D Ex tD A21 IP66/IP67 T200ºC to T85ºC

 

UK Time - GMT:

KSX Heat Tracing Cable
Thermon KSX Heat Tracing Cable

Heat Tracing - Thorne & Derrick