Heatfast HF1210 Heat Tracing Cable

Heat Tracing Cable

Heatfast

HF1210 - 10w/m 

Suitable For Pipework Frost Protection 

Heatfast HF1210 heat tracing cable is self-regulating and ideal for frost protection of pipework exposed to low ambient temperatures. It is suitable for metallic and plastic pipes, tanks and vessels.

Pictured: Heatfast HF1210 Heat Tracing Cable - Self Regulating & Ideal for Frost Protection Applications 

Heatfast HF1210 Heat Tracing Cable

Heatfast HF1210 heat tracing cable has a heat output of 10w/m at 10ºC. The power output self regulates as the pipe or ambient temperature increases meaning that the cable will never overheat and is energy efficient.

In reverse, when the pipe or ambient temperature falls, the power output of the cable increases to compensate for the additional pipe heat loss. HF1210 has a maximum circuit length of 162m. 

Heatfast HF1210 Heat Tracing Cable - Technical Specification
Cable Watt Density 10w/m at 10ºC
Construction

Copper Conductors

Self-Regulating Conductive Core

Thermoplastic Elastomer Dielectric Jacket

Copper Braid

Thermoplastic Elastomer Overjacket

Supply Voltage 230V
Maximum Circuit Length 162m
Maximum Maintenance Temperature 65ºC
Maximum Continuous Exposure Temperature 85ºC
Maximum Continuous Exposure Temperature 65ºC
Minimum Bend Radius 12mm at -40ºC

Pictured: Heatfast HF1210 Heat Tracing Cable Power Rating Chart

HF1210 Trace Heating Cable Power Rating Chart

 