Aquilar's Aquitron AT-MZA Multi-Zone Alarm control panel allows for centralised monitoring of up to 8 leak detection zones comprising of leak sensing cables, Aquitron probes and sensors.
The AT-MZA can be used with water detection probes, optical oil sensors, float switches and immersion sensors. The maximum sensing circuit per zone using leak detection cable is 100m and a combination of 10 Aquitron probes.
The AT-MZA Multi-Zone Alarm triggers a visual and audible alarm in the event of a leak or a cable fault being detected. An Aquitron AT-RAP remote alarm system can also be fitted within areas such as reception desks and security rooms to provide addition notification of an alarm.
An AT-BU battery unit can be used to provide a 24 hour back up in the event of mains connection failure.
AT-MZA Multi-Zone Alarms are available for 230/120VAC and 12VDC.
Sensing Cable Compatibility | All TraceTek sensing cable (TT1000, 3000, 5000, 5001, 7000) |
---|---|
Detection Probes | Water detection probes, optical oil sensors, float switches and immersion sensors |
Maximum Sensing Circuit | 100 metres (328ft) of TraceTek sensing cable |
Enclosure | Powder coated steel, colour RAL 7032, IP54, lockable |
Humidity | 5% to 95% non-condensing |
Power Supply | 230/120VAC, 50/60Hz, 12VDC, 7 Watts |
Relay Output | Volt free relay contacts activated by leak or cable fault (NC/COM or NO/COM) |
Status LED | Power (Mains-Green, Battery-Red), Alarm (red flashing), Leak (Red), Cable break (Yellow) |
Approvals |
Electromagnetic Compatibility (EMC)
CE Compliant with standards for immunity - EN6100-6-2:1999 (Heavy industrial)
CE Compliant with standards for emissions - EN50081-1 |