MEYNELL 15/3 Thermostatic Mixing Valve
A ½" thermostatic mixing valve with integral check valves and strainers, suitable for under-basin installation and providing thermostatic shutdown in less than 2 seconds.
The unit also incorporates tamper proof temperature adjustment.
Operation:
Designed to be installed into the supply pipework and must be used with a separate outlet flow control such as a tap.
Connections:
Inlet and outlet: 15 mm compression fittings.
Pressure:
Minimum operating pressure: 0.1 bar.
Maximum static pressure: 10 bar.
Maximum pressure loss ratio: 10:1 (in favour of either supply).
Maximum hot water supply temperature: 85°C.
Maximum cold water supply temperature: 25°C.
Note: Both hot and cold pressures should be nominally equal.
Temperature range:
Factory pre-set maximum outlet temperature: 42°C.
Minimum temperature differential between hot inlet and pre-set outlet temperature: 10°C.
Optimum temperature control range: 35–45°C.
Maximum hot water temperature: 85°C (for safety reasons it is recommended that the hot water storage temperature is maintained at between 60°C and 65°C in ablutionary applications).
Materials:
Body: DZR brass housed in white plastic casing.
The T&D-8 is our most competitivly priced TMV3 approved valve and is suitable for a range of applications including health, education and commercial buildings.
The Thorne and Derrick T&D-8 valve includes integral check valves and strainers, it can be installed in any orientation provided that the hot and cold supplies are connected to the appropriate indicated installed.
The TMV Scheme certifies Type 3 thermostatic mixing valves manufactured to meet the highest specifications required by the NHS Estates D08 standard for mixing valves for use within health care premises in the United Kingdom.
The TMV Scheme also now certifies Type 2 thermostatic mixing valves for the domestic market and is working with the Child Accident Prevention Trust to promote the safe use of hot water in domestic premises.